EnerSys 3CA-3MFR POWERSAFE® C BATTERIES
Engineered to meet the requirements of the power industry, the features inherent to the PowerSafe 3CA-3MFR battery make it one of the best in the market. The CA-M battery features calcium plates which demonstrate maximized performance in long discharge applications and reduce watering requirements. The jar design allows for more free electrolyte enabling the CA-M battery to be offered with 100% initial capacity. Designed for easier maintenance, all of the posts and connectors reside above the cell cover meaning maintenance routines including cell monitoring and measurements are simplified.
The CA-M series of batteries also includes a Slide LockTM post seal that allows for natural plate growth over time. The innovative tongue-and-groove jar-to-cover seal provides reliability with a robust airtight seal. Combine the standard square plate design which enhances high rate performance and the multi-cell construction that reduces maintenance time, it is no surprise that the CA-M battery has long set the standard to which all other batteries are compared.
3CA-3MFR POWERSAFE® FEATURES AND BENEFITS
• Capacity range 50-200Ah
• Lead-calcium alloy
• Standard Styrene Acrylonitrile (SAN) jar with flame retardant UL94 V-0 PVC cover; flame retardant jar available
• Thick positive plates maximize performance in long discharge applications
• 20 year life expectancy in float service at 77°F (25°C) ambient temperature
• 2-cell jars available for strings requiring cell counts not divisible by 3
3CA-3MFR CONSTRUCTION
• 0.28" thick positive plates provide excellent long discharge rates and long life
• Square plate configuration enhances high rate performance
• Separator – microporous rubber with glass fiber retainers
• Electrolyte – dilute sulfuric acid with specific gravity of 1.215 (1.250 available upon request)
• Individual posts to monitor individual cell performance
• Flame arrestors - included for increased operational safety
3CA-3MFR CONSTRUCTION
• Space efficient footprint
• Designed to be rack-mounted with easy access to posts
• Excellent long discharge and complex duty cycle capability
• Lead-calcium design reduces maintenance (less watering) over traditional lead-antimony batteries
• All posts and connectors reside above the cell cover for easier maintenance, cell monitoring and measurements
• Operating temperature: 32°F (0°C) to 104°F (40°C) Recommended temperature: 68°F (20°C) to 86°F (30°C)
3CA-3MFR STANDARDS
• The management systems governing the manufacture of this product are ISO 9001 and ISO 14001 certified
• Optional testing in accordance to IEEE 450 or customer duty cycle available
NOTE: All inter-cell, inter-tier, inter-step, end-to-end inter-rack, back-to-back inter-rack connectors, terminal lugs, and terminal plates are included with every battery. Across-aisle inter-rack connectors are not included
Power Storage Solutions Installation and Service for 3CA-3MFR
We understand that data centers are heavily reliant on batteries for backup power. We also understand that batteries must be redundant and if only one battery in your UPS configuration is not performing; it compromises your overall backup power. Our experience and our focus is to know the batteries and their implication for your operation. To determine the perfect solution, we will partner with you, analyze your critical power needs and construct the backup power solution that will perform as designed.
We can remove and recycle your old battery system then install, properly set up and test your new system. We have been installing stationary batteries for over 20 years. We have the experience, equipment and capabilities to safely perform this type of work.
Routine maintenance ensures your UPS equipment stays reliable, improving your UPS’s overall performance and extending their useful life. Service plans allow customers to be proactive; providing opportunity to detect potential points of failure preventing expensive problems.
When ordering new batteries, also remember to properly recycle your old lead batteries. Federal and state regulations require lead-acid batteries be recycled. Power Storage Solutions’ nationwide service organization can arrange pickup, transportation to and recycling at any one of our company affiliated smelters. Click Here for More Information
For More Information from EnerSys Website: EnerSys PowerSafe CA-M
Additional Information
Weight | 57 lbs |
---|---|
Length | 7 |
Width | 9 |
Height | |
Brand | Enersys |
Battery Model | PowerSafe CA |
Equipment | Batteries |
Market | Switchgear |